MAN 150 KW Cogeneration Unit

Specification: SDPM150EI6MS4

Frequency

60 Hz

Continuous Electric Output (kw)

150

Mechanical Power (bhp)

218.5

Engine Ignition Timing (BTDC)

20

Rotation Speed (rpm)

1,800

Heat Rate (btu per KWh)

9,842

Combined Efficiency  (useful)

84.8%

electrical Efficiency (useful)

34.7%

Thermal Efficiency (useful)

50.1%

Fuel Consumption (SCFM/SCFH)

25.4/1522

Fuel Consumption (Therms per Hour)

14.76

Total Thermal Energy Output (btu/Hour)

740,657

Heat from Water Jacket (btu/Hour)

483,514

Heat From Exhaust (btu/Hour)

257,143

Exhaust Temperature ˚F (Engine Out)

1,140

Exhaust Temperature ˚F (Module Out) (approx)

294

Exhaust Flow (lbs/Hour)

1,211

Minimum Water Flow Rate (gpm)

103.5

 Maximum cogen outlet Temperature ˚F

195

Minimum Cogen Inlet Temperature ˚F

176

Maximum Jacketwater temperature ˚F

190

Glycol concentration

40% by  Vol

Maximum Internal cabinet temperature ˚F

176

combustion air full load flow, scfm

256

Combustion Air Full Load flow, lb/hr

1,150

Gas pressure to cabinet (static to full load) (inwc)

26.6 to 29.4



Generator Electrical Output

 

Voltage

120/208
120/240
277/480
3 Phase

Type Single bearing, Directcoupled, continuous

Power Factor

Synchronous. Variable from .8 lagging to .8 leading



Operating Modes

  • Grid Independent
  • Standby
  • Parallel with Grid


Environmental

 

NOx

<0.15 g/bhp-hr (< 9 ppm)
Meets Carb 7 with Optional Catalyst

CO

<0.60 g/bhp-hr (< 84 ppm)
Meets Carb 7 with Optional Catalyst

VOC

<0.15 g/bhp-hr Meets Carb 7 with Optional Catalyst

HRC

<0.15 g/bhp-hr

Noise

<82 DBA
Lower DBA Available with Optional Components



Fuel

 

Type

Natural Gas

Standard

905 BTU/SCF LHV

Minimum Gas Pressure to Cabinet

28 Inches Water  Inlet to Cabinet



Package Size

 

Dimensions (L x W x H)

106" x 48" x 86" Without Catalyst

Dimensions (L x W x H)

106" x 48" x 112" With Catalyst

Minimum Clearances

42" Sides     18" Top

Weight

10,600 lbs



 
   
Co-Energy America, Inc.
12 Southville Road
Southborough, Massachusetts 01772

 